Testing Method :
First of all clean valve and shoulder of the cylinder  to make sure connecting portion are free from dust and other contaminants by carefully wiping using a clean, dry cloth. Remove the dust cap to clean the valve then replace the cap loosely.
 

Then Lay down the cylinder under test on its side in a rack, such that the valve end is protruding.

 

Testing procedure begin with by Using measuring cylinder to take 25 ml of the RXSOL-66-6201-500 test solution into a polythene bag, Pl. be note A control quantities of sample is necessary, which is made by introducing 25 ml of test solution. Then follow these step :::

 

1) Attach the open end of the bag over the valve head and attach it to the cylinder body. Tighten Polythene bags using one or more elastic bands. Make sure there are no air gaps in the seal. And also try to hang polythene bag minimum 20 cm off the valve end of the cylinder with the test solution in one corner.

 

2) Maintain the test for a period of not less than 4 hours and not more than 4.5 hours.

 

                            

Final Observations

1) The presence of a leak of carbon dioxide from the cylinder will cause the pink colour to the test solution to be lost and the test solution will become water white.

 

2) If no colour change is observed there is no leak of gas from cylinder. 

RX MARINE INTERNATIONAL is most popular chemicals source in INDIA, Keeping ready stock at 5 LOCATION which includes Mumbai, Kandla - Gandhidham, Vizag - Visakhapatnam, Ennore - Chennai, Kolkata more then 3000 types of chemicals. Please click here to get PRODUCT Categories details http://rxmarine.com/Products

 

Mail Us for any PRODUCT related information and purchase inquiry : mail@rxmarine.com ( This mail is for customer / Buyer only ) And if you wants to add your hand as a supplier, And if you have volume manufacturing capacity of chemicals, pl. drop your mail at rxmarine@gmail.com ( This mail is for supplier only )